    Circuit breaker ComPact NS800N 33469, 50 kA at 415 VAC, Micrologic 2.0 trip unit, 800 A, fixed, 4 poles 4
    This Compact NS800N is a complete 4 poles fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 50kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. The circuit breaker can be manually operated with ON, OFF or “push to trip” buttons. This product embeds an electronic Micrologic 2.0 trip unit, with 800A rating. Micrologic 2.0 trip unit provides adjustable long time and instantaneous protections. This 4 poles version (327mm x 280mm x 147mm) comes with a variety of optional functions and accessories. It is compliant with IEC 69947-1 and IEC60947-2 international standards and marine specifications. Compact NS800N is part of Schneider Electric EcoStruxure Power architecture.

    Specifications
    Main
    Range :- ComPact
    Product name :- ComPact NS
    range of product :- ComPact NS630b…1600
    Device short name :- Compact NS800N
    Product or component typee :- Circuit breaker
    Device application :- Distribution
    Number of poles :- 4P
    Protected poles description :- 4D
    Neutral position :- Left
    (In) rated current up to 65 °C :- 800 A at 50 °C
    [Ue] rated operational voltage :- 690 V AC 50/60 Hz
    Network type :- AC
    Network frequency :- 50/60 Hz
    Suitability for isolation :- Yes conforming to EN/IEC 60947-2
    utilisation category :- Category B
    [Icu] rated ultimate short-circuit breaking capacity :- 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    :- 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    :- 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    :- 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    :- 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
    Performance level :- N 50 kA 415 V AC
    Trip unit name :- MicroLogic 2.0
    Trip unit technology :- Electronic
    Trip unit protection functions :- LI
    control type :- Rotary handle
    :- Toggle
    Circuit breaker mounting mode :- Fixed
    Complementary
    [Ui] rated insulation voltage :- 800 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage :- 8 kV conforming to IEC 60947-2
    [Ics] rated service short-circuit breaking capacity :- 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
    :- 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
    :- 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    :- 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    :- 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    [Icw] rated short-time withstand current :- 19.2 kA 1 s conforming to IEC 60947-2
    Mechanical durability :- 10000 cycles
    Electrical durability :- 2000 cycles at 690 V In
    :- 4000 cycles at 690 V In/2
    :- 5000 cycles at 440 V In
    :- 6000 cycles at 440 V In/2
    Power losses :- 15 W
    mounting support :- Backplate
    Upside connection :- Front
    downside connection :- Front
    Connection pitch :- 70 mm
    Protection type :- L : for overload protection (long time)
    :- I : for instantaneous short-circuit protection
    Trip unit rating :- 800 A at 50 °C
    Long-time pick-up adjustment type Ir (thermal protection) :- Adjustable 9 settings
    [Ir] long-time protection pick-up adjustment range :- 0.4…1 x In
    Long-time protection delay adjustment type tr :- Adjustable 9 settings
    [tr] long-time protection delay adjustment range :- 12.5…600 s at 1.5 x Ir
    :- 0.5…24 s at 6 x Ir
    :- 0.7…16.6 s at 7.2 x Ir
    thermal memory :- 20 mn
    Instantaneous protection pick-up adjustment type Ii :- Adjustable
    [Ii] instantaneous protection pick-up adjustment range :- 1.5…10 x Ir
    earth-leakage protection :- Without
    Neutral protection settings :- No protection (3D)
    :- 0.5 x Ir (3D + N/2)
    :- 1 x Ir (4D)
    Zone selective interlocking ZSI :- Without
    Auxiliary contact composition :- 1 NO/NC
    Local signalling :- 4 LEDs (red) for fault indication
    :- 1 LED (yellow) for overload
    Width (W) :- 280 mm
    Height (H) :- 327 mm
    Depth (D) :- 147 mm
    Net weight :- 18 kg
    Environment
    Standards :- EN/IEC 60947-2
    product certifications :- ASEFA
    :- ASTA
    Pollution degree :- 3 conforming to IEC 60947
    IP degree of protection :- IP40 conforming to IEC 60529
    IK degree of protection :- IK07 conforming to EN 50102
    ambient air temperature for operation :- -25…70 °C
    Ambient air temperature for storage :- -50…85 °C
    Relative humidity :- 0…95 %
    Operating altitude :- 0…2000 m without derating
    :- 2000 m…5000 m with derating
    Packing Units
    Unit Type of Package 1 :- PCE
    Number of Units in Package 1 :- 1
    Package 1 Height :- 30.000 cm
    Package 1 Width :- 40.000 cm
    Package 1 Length :- 60.000 cm
    Package 1 Weight :- 15.640 kg

    Reviews

    There are no reviews yet.

    Be the first to review “NS800N 33469-Circuit Breaker Compact- Micrologic 2.0 – 800 A – 4 poles 4t”

    Your email address will not be published. Required fields are marked *