Circuit breaker ComPact NS1000N, 50 kA at 415 VAC, Micrologic 2.0 trip unit, 1000 A, fixed,4 poles 4d

Specification

Main
range
ComPact
 
product name
ComPact NS
 
range of product
ComPact NS630b...1600
 
device short name
Compact NS1000N
 
product or component type
Circuit breaker
 
device application
Distribution
 
Number of poles
4P
 
protected poles description
4d
 
neutral position
Left
 
(In) rated current up to 65 °C
1000 A at 50 °C
 
[Ue] rated operational voltage
690 V AC 50/60 Hz
 
network type
AC
 
network frequency
50/60 Hz
 
suitability for isolation
Yes conforming to EN/IEC 60947-2
 
utilisation category
Category B
 
[Icu] rated ultimate short-circuit breaking capacity
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
 
Performance level
N 50 kA 415 V AC
 
trip unit name
Micrologic 2.0
 
trip unit technology
Electronic
 
trip unit protection functions
LI
 
control type
Rotary handle
Toggle
 
Circuit breaker mounting mode
Fixed
 
Complementary
[Ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
 
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
 
[Ics] rated service short-circuit breaking capacity
30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
 
[Icw] rated short-time withstand current
19.2 kA 1 s conforming to IEC 60947-2
 
mechanical durability
10000 cycles
 
electrical durability
2000 cycles at 690 V In
4000 cycles at 690 V In/2
5000 cycles at 440 V In
6000 cycles at 440 V In/2
 
power losses
22 W
 
mounting support
Backplate
 
upside connection
Front
 
downside connection
Front
 
connection pitch
70 mm
 
protection type
L : for overload protection (long time)
I : for instantaneous short-circuit protection
 
trip unit rating
1000 A at 50 °C
 
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
 
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
 
Long-time protection delay adjustment type tr
Adjustable 9 settings
 
[tr] long-time protection delay adjustment range
12.5…600 s at 1.5 x Ir
0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
 
thermal memory
20 mn
 
Instantaneous protection pick-up adjustment type Ii
Adjustable
 
[Ii] instantaneous protection pick-up adjustment range
1.5...10 x Ir
 
earth-leakage protection
Without
 
Neutral protection settings
No protection (3d)
0.5 x Ir (3d + N/2)
1 x Ir (4d)
 
auxiliary contact composition
1 NO/NC
 
local signalling
4 LEDs (red) for fault indication
1 LED (yellow) for overload
 
Width (W)
280 mm
 
Height (H)
327 mm
 
Depth (D)
147 mm
 
net weight
18 kg